Ordem de trabalho Conversor de freqüência

Work order: Parameterize the frequency inverter              

auxiliary aid:   Technical Data Manual

Work Order VFD

Work Order VFD

In order to enable a smooth start and stop, the drive for the conveyor belt is controlled by a VFD. Your work order is to understand the information of the motor rating plate and to determine the correct parameters for the VFD.

Motor rating plate of a 3 Phase Induction motor

Motor rating plate of a 3 Phase Induction motor

A1: Explain the information given on the rating plate.
A2:  How should the motor be switched on our three-phase network 400 V / 230 V if you would connect it directly (Star or Delta)? Please give a short explanation!
A3:  Determine slip, slip speed and efficiency for nominal operation and operating frequency f = 50 Hz.
A4:  So that the belt starts and stops smoothly, choose a frequency converter. According to the manufacturer, the following motor parameters must be entered for initial commissioning:

P0304: nominal voltage
P0305: nominal current
P0307: nominal power
P0308: nominal power factor
P0310: nominal frequency
P0311: nominal speed

Enter the specific values. Missing values you have to calculate.

A5: The workpiece carriers (workpiece carriers) should be conveyed at a maximum speed of 0.4 m/s. For starting the acceleration for the belt should be 0.10 m/s2. When stopping, the deceleration should be 0.25 m/s2. To which values do you have to set the VFD parameters P0320 (ramp-up time) and P0321 (ramp-down time)?

Determination of start-stop time for belt drive

Determination of start-stop time for belt drive

 

=>  Solution Work order VFD